Single loop CDU w/ RDHx
- The maximum capacity of a single cabinet is 10kW/6kW
- No need for external ice water, no condensation
- No need for chiller and pipeline, high flexibility of placement
- Provides optimal liquid-to-air heat exchange with RDHx
- Applicable to all kinds of water-cooled communication or water-cooled servers and other equipment, the best choice for single cabinet heat dissipation
Components
- Standard Cabinet*1
- Active cooling RDHx
- Air-liquid LCSU height@5U/4U
- Water supply/return manifold
Product description
M/N | ATD010 | ATD006 |
Size(W x L) | 42U , 600mm( W ) x 1200mm( L ) | 42U , 600mm( W ) x 1200mm( L ) |
RDHx M/N | TD28F | TD18F |
Manifold | 1 VS 10 | 1 VS 8 |
Coolent | Coolant THC-00 | Coolant THC-00 |
Coolent capacity | 10.0 L | 5.7 L |
Coolent flow rate | Up to 56.8 LPM | Up to 45 LPM |
Inlet Coolent temperature | Above Dew Point | Above Dew Point |
Max. Pressure | 690 kPa ( 100 psl) | 690 kPa ( 100 psl) |
Weight of RDHx W/coolent | 133 kg | 113 kg |
System flow rate | 56.8 LPM | 45 LPM |
Fan operating Voltage | DC 24V | DC 24V |
TTL Fan power consumption | 39.6 W | 26.4 W |
Fan size( L x W x H ) | 80 x 80 x 38 cm | 80 x 80 x 38 cm |
Fan Noise | 66.5 dB(A) | 66.5 dB(A) |
Fan Max RPM | 12000 rpm | 12000 rpm |
Number of fan | 12 pcs | 8 pcs |
TTL Fan Flow rate | 1720 CFM | 1150 CFM |
CE certification | Yes | Yes |
LCSU’s M/N | 5U/4U | 5U/4U |
LCSUPump | Dual redundant inverter pump (1+1) | Dual redundant inverter pump (1+1) |
Ambient temperature | 25~27 ℃ | 25~27 ℃ |
Humidity | 40~65 %RH | 40~65 %RH |
Capacity per Cabinet | 10 kW | 6kW |